0 to 1200°C, K type
0 to 200°C, RTD type
0 to 400°C, RTD type
TEMPERATURE SET POINTS :
1 potentiometric set point.
|
SE-200-K
SE-200-RTD200
SE-200-RTD400
|
Rs.
675/-
Rs. 675/-
Rs. 675/-
|
|

|
|
SE - 200-
|
|
Under
normal conditions, the temperature at the tip of sensor is displayed.
when push button on front panel is pressed, temperature reading set by
the corresponding potentiometer, is displayed.
|
ACCURACY
:
± 0.5% of range ± 1°C from 0 to 1000°C.
± 1% of range ± 2°C from 1000 to 1100°C.
± 2% of range ± 2°C from 1100 to 1200°C.
All controllers have automatic room temperature compensation. RTD
type controllers have 3 wire system for automatic compensation of
sensor cable effects.
|
|
|
CONTROL ACTION
|
ON/OFF
with accuracy of ±1°C.
|
|
OUTPUT
|
1
N.O. and 1 N.C. relay contacts of contact rating 5A/230VAC for
resistance load.
|
|
TYPE OF SENSORS
|
Chromel
alumel type K (Cr-Al) thermocouple sensors for 200-K. Suitable sensors
are TC-SK1 and TC-23K. (Refer to catalog of sensors for details).
RTD (PT100) type of sensors for 200-RTD200, 200-RTD400. Suitable
sensors are RTD-52 and RTD-53. (Refer to catalog of sensors for
details).
|
|
DISPLAY
|
3½ digit, 7
segment bright LED type of 12.5mm height. Decimal point, over-range
and negative polarity indications are provided. Open sensors
indications 1 in most significant digit and blanks for the remaining
3 digits.
|
|
POWER REQUIREMENTS
|
230
± 10% volts AC, 50/60 Hertz, 5VA.
|
|
SIZE AND WEIGHT
|
96mm
(H) x 96mm (W) x 110mm (D) with panel cutout of 92mm (H) x 92mm (W).
600 gms.
|
|
STANDARD ACCESSORIES
|
Instruction
manual.
|
|